# Modbus Input Plugin
|
2020-01-29 18:18:58 +08:00
|
|
|
|
2020-04-22 02:27:35 +08:00
|
|
|
The Modbus plugin collects Discrete Inputs, Coils, Input Registers and Holding
|
|
|
|
|
Registers via Modbus TCP or Modbus RTU/ASCII.
|
2020-01-29 18:18:58 +08:00
|
|
|
|
2022-04-12 05:32:25 +08:00
|
|
|
## Configuration
|
2020-01-29 18:18:58 +08:00
|
|
|
|
2022-05-24 21:49:47 +08:00
|
|
|
```toml @sample_general_begin.conf @sample_register.conf @sample_request.conf @sample_general_end.conf
|
2022-04-12 05:32:25 +08:00
|
|
|
# Retrieve data from MODBUS slave devices
|
2020-04-22 02:27:35 +08:00
|
|
|
[[inputs.modbus]]
|
|
|
|
|
## Connection Configuration
|
|
|
|
|
##
|
2021-08-04 05:09:51 +08:00
|
|
|
## The plugin supports connections to PLCs via MODBUS/TCP, RTU over TCP, ASCII over TCP or
|
2020-04-22 02:27:35 +08:00
|
|
|
## via serial line communication in binary (RTU) or readable (ASCII) encoding
|
|
|
|
|
##
|
|
|
|
|
## Device name
|
|
|
|
|
name = "Device"
|
|
|
|
|
|
|
|
|
|
## Slave ID - addresses a MODBUS device on the bus
|
|
|
|
|
## Range: 0 - 255 [0 = broadcast; 248 - 255 = reserved]
|
|
|
|
|
slave_id = 1
|
|
|
|
|
|
|
|
|
|
## Timeout for each request
|
|
|
|
|
timeout = "1s"
|
|
|
|
|
|
|
|
|
|
## Maximum number of retries and the time to wait between retries
|
|
|
|
|
## when a slave-device is busy.
|
|
|
|
|
# busy_retries = 0
|
|
|
|
|
# busy_retries_wait = "100ms"
|
|
|
|
|
|
|
|
|
|
# TCP - connect via Modbus/TCP
|
|
|
|
|
controller = "tcp://localhost:502"
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2020-04-22 02:27:35 +08:00
|
|
|
## Serial (RS485; RS232)
|
|
|
|
|
# controller = "file:///dev/ttyUSB0"
|
|
|
|
|
# baud_rate = 9600
|
|
|
|
|
# data_bits = 8
|
|
|
|
|
# parity = "N"
|
|
|
|
|
# stop_bits = 1
|
|
|
|
|
|
2021-08-04 05:09:51 +08:00
|
|
|
## For Modbus over TCP you can choose between "TCP", "RTUoverTCP" and "ASCIIoverTCP"
|
|
|
|
|
## default behaviour is "TCP" if the controller is TCP
|
|
|
|
|
## For Serial you can choose between "RTU" and "ASCII"
|
|
|
|
|
# transmission_mode = "RTU"
|
2020-04-22 02:27:35 +08:00
|
|
|
|
2021-10-20 05:12:13 +08:00
|
|
|
## Trace the connection to the modbus device as debug messages
|
|
|
|
|
## Note: You have to enable telegraf's debug mode to see those messages!
|
|
|
|
|
# debug_connection = false
|
|
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
## Define the configuration schema
|
|
|
|
|
## |---register -- define fields per register type in the original style (only supports one slave ID)
|
|
|
|
|
## |---request -- define fields on a requests base
|
|
|
|
|
configuration_type = "register"
|
|
|
|
|
|
|
|
|
|
## --- "register" configuration style ---
|
|
|
|
|
|
2020-04-22 02:27:35 +08:00
|
|
|
## Measurements
|
|
|
|
|
##
|
|
|
|
|
|
|
|
|
|
## Digital Variables, Discrete Inputs and Coils
|
2020-07-28 04:48:44 +08:00
|
|
|
## measurement - the (optional) measurement name, defaults to "modbus"
|
|
|
|
|
## name - the variable name
|
|
|
|
|
## address - variable address
|
2020-04-22 02:27:35 +08:00
|
|
|
|
|
|
|
|
discrete_inputs = [
|
2020-07-28 04:48:44 +08:00
|
|
|
{ name = "start", address = [0]},
|
|
|
|
|
{ name = "stop", address = [1]},
|
|
|
|
|
{ name = "reset", address = [2]},
|
|
|
|
|
{ name = "emergency_stop", address = [3]},
|
2020-04-22 02:27:35 +08:00
|
|
|
]
|
|
|
|
|
coils = [
|
2020-07-28 04:48:44 +08:00
|
|
|
{ name = "motor1_run", address = [0]},
|
|
|
|
|
{ name = "motor1_jog", address = [1]},
|
|
|
|
|
{ name = "motor1_stop", address = [2]},
|
2020-04-22 02:27:35 +08:00
|
|
|
]
|
|
|
|
|
|
|
|
|
|
## Analog Variables, Input Registers and Holding Registers
|
|
|
|
|
## measurement - the (optional) measurement name, defaults to "modbus"
|
2020-07-28 04:48:44 +08:00
|
|
|
## name - the variable name
|
|
|
|
|
## byte_order - the ordering of bytes
|
2020-04-22 02:27:35 +08:00
|
|
|
## |---AB, ABCD - Big Endian
|
|
|
|
|
## |---BA, DCBA - Little Endian
|
|
|
|
|
## |---BADC - Mid-Big Endian
|
|
|
|
|
## |---CDAB - Mid-Little Endian
|
2021-12-03 06:06:06 +08:00
|
|
|
## data_type - INT16, UINT16, INT32, UINT32, INT64, UINT64,
|
|
|
|
|
## FLOAT32-IEEE, FLOAT64-IEEE (the IEEE 754 binary representation)
|
|
|
|
|
## FLOAT32, FIXED, UFIXED (fixed-point representation on input)
|
|
|
|
|
## scale - the final numeric variable representation
|
|
|
|
|
## address - variable address
|
2020-04-22 02:27:35 +08:00
|
|
|
|
|
|
|
|
holding_registers = [
|
2020-07-28 04:48:44 +08:00
|
|
|
{ name = "power_factor", byte_order = "AB", data_type = "FIXED", scale=0.01, address = [8]},
|
|
|
|
|
{ name = "voltage", byte_order = "AB", data_type = "FIXED", scale=0.1, address = [0]},
|
|
|
|
|
{ name = "energy", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [5,6]},
|
|
|
|
|
{ name = "current", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [1,2]},
|
|
|
|
|
{ name = "frequency", byte_order = "AB", data_type = "UFIXED", scale=0.1, address = [7]},
|
|
|
|
|
{ name = "power", byte_order = "ABCD", data_type = "UFIXED", scale=0.1, address = [3,4]},
|
2020-04-22 02:27:35 +08:00
|
|
|
]
|
|
|
|
|
input_registers = [
|
2020-07-28 04:48:44 +08:00
|
|
|
{ name = "tank_level", byte_order = "AB", data_type = "INT16", scale=1.0, address = [0]},
|
|
|
|
|
{ name = "tank_ph", byte_order = "AB", data_type = "INT16", scale=1.0, address = [1]},
|
|
|
|
|
{ name = "pump1_speed", byte_order = "ABCD", data_type = "INT32", scale=1.0, address = [3,4]},
|
2020-04-22 02:27:35 +08:00
|
|
|
]
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
## --- "request" configuration style ---
|
|
|
|
|
|
|
|
|
|
## Per request definition
|
|
|
|
|
##
|
|
|
|
|
|
|
|
|
|
## Define a request sent to the device
|
|
|
|
|
## Multiple of those requests can be defined. Data will be collated into metrics at the end of data collection.
|
|
|
|
|
[[inputs.modbus.request]]
|
|
|
|
|
## ID of the modbus slave device to query.
|
|
|
|
|
## If you need to query multiple slave-devices, create several "request" definitions.
|
|
|
|
|
slave_id = 1
|
|
|
|
|
|
|
|
|
|
## Byte order of the data.
|
|
|
|
|
## |---ABCD -- Big Endian (Motorola)
|
|
|
|
|
## |---DCBA -- Little Endian (Intel)
|
|
|
|
|
## |---BADC -- Big Endian with byte swap
|
|
|
|
|
## |---CDAB -- Little Endian with byte swap
|
|
|
|
|
byte_order = "ABCD"
|
|
|
|
|
|
|
|
|
|
## Type of the register for the request
|
|
|
|
|
## Can be "coil", "discrete", "holding" or "input"
|
|
|
|
|
register = "coil"
|
|
|
|
|
|
|
|
|
|
## Name of the measurement.
|
|
|
|
|
## Can be overriden by the individual field definitions. Defaults to "modbus"
|
|
|
|
|
# measurement = "modbus"
|
|
|
|
|
|
|
|
|
|
## Field definitions
|
|
|
|
|
## Analog Variables, Input Registers and Holding Registers
|
|
|
|
|
## address - address of the register to query. For coil and discrete inputs this is the bit address.
|
|
|
|
|
## name *1 - field name
|
|
|
|
|
## type *1,2 - type of the modbus field, can be INT16, UINT16, INT32, UINT32, INT64, UINT64 and
|
|
|
|
|
## FLOAT32, FLOAT64 (IEEE 754 binary representation)
|
|
|
|
|
## scale *1,2 - (optional) factor to scale the variable with
|
|
|
|
|
## output *1,2 - (optional) type of resulting field, can be INT64, UINT64 or FLOAT64. Defaults to FLOAT64 if
|
|
|
|
|
## "scale" is provided and to the input "type" class otherwise (i.e. INT* -> INT64, etc).
|
|
|
|
|
## measurement *1 - (optional) measurement name, defaults to the setting of the request
|
|
|
|
|
## omit - (optional) omit this field. Useful to leave out single values when querying many registers
|
|
|
|
|
## with a single request. Defaults to "false".
|
|
|
|
|
##
|
|
|
|
|
## *1: Those fields are ignored if field is omitted ("omit"=true)
|
|
|
|
|
##
|
|
|
|
|
## *2: Thise fields are ignored for both "coil" and "discrete"-input type of registers. For those register types
|
|
|
|
|
## the fields are output as zero or one in UINT64 format by default.
|
|
|
|
|
|
|
|
|
|
## Coil / discrete input example
|
|
|
|
|
fields = [
|
|
|
|
|
{ address=0, name="motor1_run"},
|
|
|
|
|
{ address=1, name="jog", measurement="motor"},
|
|
|
|
|
{ address=2, name="motor1_stop", omit=true},
|
|
|
|
|
{ address=3, name="motor1_overheating"},
|
|
|
|
|
]
|
|
|
|
|
|
2022-07-26 05:14:57 +08:00
|
|
|
[inputs.modbus.request.tags]
|
2021-12-09 03:19:13 +08:00
|
|
|
machine = "impresser"
|
|
|
|
|
location = "main building"
|
|
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
[[inputs.modbus.request]]
|
|
|
|
|
## Holding example
|
|
|
|
|
## All of those examples will result in FLOAT64 field outputs
|
|
|
|
|
slave_id = 1
|
|
|
|
|
byte_order = "DCBA"
|
|
|
|
|
register = "holding"
|
|
|
|
|
fields = [
|
|
|
|
|
{ address=0, name="voltage", type="INT16", scale=0.1 },
|
|
|
|
|
{ address=1, name="current", type="INT32", scale=0.001 },
|
|
|
|
|
{ address=3, name="power", type="UINT32", omit=true },
|
|
|
|
|
{ address=5, name="energy", type="FLOAT32", scale=0.001, measurement="W" },
|
|
|
|
|
{ address=7, name="frequency", type="UINT32", scale=0.1 },
|
|
|
|
|
{ address=8, name="power_factor", type="INT64", scale=0.01 },
|
|
|
|
|
]
|
|
|
|
|
|
2022-07-26 05:14:57 +08:00
|
|
|
[inputs.modbus.request.tags]
|
2021-12-09 03:19:13 +08:00
|
|
|
machine = "impresser"
|
|
|
|
|
location = "main building"
|
|
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
[[inputs.modbus.request]]
|
|
|
|
|
## Input example with type conversions
|
|
|
|
|
slave_id = 1
|
|
|
|
|
byte_order = "ABCD"
|
|
|
|
|
register = "input"
|
|
|
|
|
fields = [
|
|
|
|
|
{ address=0, name="rpm", type="INT16" }, # will result in INT64 field
|
|
|
|
|
{ address=1, name="temperature", type="INT16", scale=0.1 }, # will result in FLOAT64 field
|
|
|
|
|
{ address=2, name="force", type="INT32", output="FLOAT64" }, # will result in FLOAT64 field
|
|
|
|
|
{ address=4, name="hours", type="UINT32" }, # will result in UIN64 field
|
2022-04-12 05:32:25 +08:00
|
|
|
]
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-07-26 05:14:57 +08:00
|
|
|
[inputs.modbus.request.tags]
|
2021-12-09 03:19:13 +08:00
|
|
|
machine = "impresser"
|
|
|
|
|
location = "main building"
|
|
|
|
|
|
2021-10-20 05:12:13 +08:00
|
|
|
## Enable workarounds required by some devices to work correctly
|
|
|
|
|
# [inputs.modbus.workarounds]
|
2022-10-19 02:42:18 +08:00
|
|
|
## Pause after connect delays the first request by the specified time. This might be necessary for (slow) devices.
|
|
|
|
|
# pause_after_connect = "0ms"
|
2021-10-20 05:12:13 +08:00
|
|
|
## Pause between read requests sent to the device. This might be necessary for (slow) serial devices.
|
|
|
|
|
# pause_between_requests = "0ms"
|
|
|
|
|
## Close the connection after every gather cycle. Usually the plugin closes the connection after a certain
|
|
|
|
|
## idle-timeout, however, if you query a device with limited simultaneous connectivity (e.g. serial devices)
|
|
|
|
|
## from multiple instances you might want to only stay connected during gather and disconnect afterwards.
|
|
|
|
|
# close_connection_after_gather = false
|
2020-01-29 18:18:58 +08:00
|
|
|
```
|
2020-04-22 02:27:35 +08:00
|
|
|
|
2021-11-25 03:18:53 +08:00
|
|
|
## Notes
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
You can debug Modbus connection issues by enabling `debug_connection`. To see
|
|
|
|
|
those debug messages, Telegraf has to be started with debugging enabled
|
|
|
|
|
(i.e. with the `--debug` option). Please be aware that connection tracing will
|
|
|
|
|
produce a lot of messages and should __NOT__ be used in production environments.
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2022-10-19 02:42:18 +08:00
|
|
|
Please use `pause_after_connect` / `pause_between_requests` with care. Ensure
|
|
|
|
|
the total gather time, including the pause(s), does not exceed the configured
|
|
|
|
|
collection interval. Note that pauses add up if multiple requests are sent!
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
## Configuration styles
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
The modbus plugin supports multiple configuration styles that can be set using
|
|
|
|
|
the `configuration_type` setting. The different styles are described
|
|
|
|
|
below. Please note that styles cannot be mixed, i.e. only the settings belonging
|
|
|
|
|
to the configured `configuration_type` are used for constructing _modbus_
|
|
|
|
|
requests and creation of metrics.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
Directly jump to the styles:
|
|
|
|
|
|
|
|
|
|
- [original / register plugin style](#register-configuration-style)
|
|
|
|
|
- [per-request style](#request-configuration-style)
|
|
|
|
|
|
|
|
|
|
---
|
|
|
|
|
|
|
|
|
|
### `register` configuration style
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
This is the original style used by this plugin. It allows a per-register
|
|
|
|
|
configuration for a single slave-device.
|
2020-04-22 02:27:35 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
#### Usage of `data_type`
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
The field `data_type` defines the representation of the data value on input from
|
|
|
|
|
the modbus registers. The input values are then converted from the given
|
|
|
|
|
`data_type` to a type that is apropriate when sending the value to the output
|
|
|
|
|
plugin. These output types are usually one of string, integer or
|
|
|
|
|
floating-point-number. The size of the output type is assumed to be large enough
|
|
|
|
|
for all supported input types. The mapping from the input type to the output
|
|
|
|
|
type is fixed and cannot be configured.
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
##### Integers: `INT16`, `UINT16`, `INT32`, `UINT32`, `INT64`, `UINT64`
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
These types are used for integer input values. Select the one that matches your
|
|
|
|
|
modbus data source.
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
##### Floating Point: `FLOAT32-IEEE`, `FLOAT64-IEEE`
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
Use these types if your modbus registers contain a value that is encoded in this
|
|
|
|
|
format. These types always include the sign, therefore no variant exists.
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
##### Fixed Point: `FIXED`, `UFIXED` (`FLOAT32`)
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
These types are handled as an integer type on input, but are converted to
|
|
|
|
|
floating point representation for further processing (e.g. scaling). Use one of
|
|
|
|
|
these types when the input value is a decimal fixed point representation of a
|
|
|
|
|
non-integer value.
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
Select the type `UFIXED` when the input type is declared to hold unsigned
|
|
|
|
|
integer values, which cannot be negative. The documentation of your modbus
|
|
|
|
|
device should indicate this by a term like 'uint16 containing fixed-point
|
|
|
|
|
representation with N decimal places'.
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
Select the type `FIXED` when the input type is declared to hold signed integer
|
|
|
|
|
values. Your documentation of the modbus device should indicate this with a term
|
|
|
|
|
like 'int32 containing fixed-point representation with N decimal places'.
|
2020-07-28 04:48:44 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
(FLOAT32 is deprecated and should not be used. UFIXED provides the same
|
|
|
|
|
conversion from unsigned values).
|
2020-04-22 02:27:35 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
---
|
|
|
|
|
|
|
|
|
|
### `request` configuration style
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
This sytle can be used to specify the modbus requests directly. It enables
|
|
|
|
|
specifying multiple `[[inputs.modbus.request]]` sections including multiple
|
|
|
|
|
slave-devices. This way, _modbus_ gateway devices can be queried. Please note
|
|
|
|
|
that _requests_ might be split for non-consecutive addresses. If you want to
|
|
|
|
|
avoid this behavior please add _fields_ with the `omit` flag set filling the
|
|
|
|
|
gaps between addresses.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
#### Slave device
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
You can use the `slave_id` setting to specify the ID of the slave device to
|
|
|
|
|
query. It should be specified for each request, otherwise it defaults to
|
|
|
|
|
zero. Please note, only one `slave_id` can be specified per request.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
#### Byte order of the register
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
The `byte_order` setting specifies the byte and word-order of the registers. It
|
|
|
|
|
can be set to `ABCD` for _big endian (Motorola)_ or `DCBA` for _little endian
|
|
|
|
|
(Intel)_ format as well as `BADC` and `CDAB` for _big endian_ or _little endian_
|
|
|
|
|
with _byte swap_.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
#### Register type
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
The `register` setting specifies the modbus register-set to query and can be set
|
|
|
|
|
to `coil`, `discrete`, `holding` or `input`.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
#### Per-request measurement setting
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
You can specify the name of the measurement for the following field definitions
|
|
|
|
|
using the `measurement` setting. If the setting is omitted `modbus` is
|
|
|
|
|
used. Furthermore, the measurement value can be overridden by each field
|
|
|
|
|
individually.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
#### Field definitions
|
|
|
|
|
|
|
|
|
|
Each `request` can contain a list of fields to collect from the modbus device.
|
|
|
|
|
|
|
|
|
|
##### address
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
A field is identified by an `address` that reflects the modbus register
|
|
|
|
|
address. You can usually find the address values for the different datapoints in
|
|
|
|
|
the datasheet of your modbus device. This is a mandatory setting.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
For _coil_ and _discrete input_ registers this setting specifies the __bit__
|
|
|
|
|
containing the value of the field.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
##### name
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
Using the `name` setting you can specify the field-name in the metric as output
|
|
|
|
|
by the plugin. This setting is ignored if the field's `omit` is set to `true`
|
|
|
|
|
and can be omitted in this case.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
__Please note:__ There cannot be multiple fields with the same `name` in one
|
|
|
|
|
metric identified by `measurement`, `slave_id` and `register`.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
##### register datatype
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
The `register` setting specifies the datatype of the modbus register and can be
|
|
|
|
|
set to `INT16`, `UINT16`, `INT32`, `UINT32`, `INT64` or `UINT64` for integer
|
|
|
|
|
types or `FLOAT32` and `FLOAT64` for IEEE 754 binary representations of floating
|
|
|
|
|
point values. Usually the datatype of the register is listed in the datasheet of
|
|
|
|
|
your modbus device in relation to the `address` described above.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
This setting is ignored if the field's `omit` is set to `true` or if the
|
|
|
|
|
`register` type is a bit-type (`coil` or `discrete`) and can be omitted in
|
|
|
|
|
these cases.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
##### scaling
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
You can use the `scale` setting to scale the register values, e.g. if the
|
|
|
|
|
register contains a fix-point values in `UINT32` format with two decimal places
|
|
|
|
|
for example. To convert the read register value to the actual value you can set
|
|
|
|
|
the `scale=0.01`. The scale is used as a factor e.g. `field_value * scale`.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
This setting is ignored if the field's `omit` is set to `true` or if the
|
|
|
|
|
`register` type is a bit-type (`coil` or `discrete`) and can be omitted in these
|
|
|
|
|
cases.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
__Please note:__ The resulting field-type will be set to `FLOAT64` if no output
|
|
|
|
|
format is specified.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
##### output datatype
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
Using the `output` setting you can explicitly specify the output
|
|
|
|
|
field-datatype. The `output` type can be `INT64`, `UINT64` or `FLOAT64`. If not
|
|
|
|
|
set explicitly, the output type is guessed as follows: If `scale` is set to a
|
|
|
|
|
non-zero value, the output type is `FLOAT64`. Otherwise, the output type
|
|
|
|
|
corresponds to the register datatype _class_, i.e. `INT*` will result in
|
|
|
|
|
`INT64`, `UINT*` in `UINT64` and `FLOAT*` in `FLOAT64`.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
This setting is ignored if the field's `omit` is set to `true` or if the
|
|
|
|
|
`register` type is a bit-type (`coil` or `discrete`) and can be omitted in these
|
|
|
|
|
cases. For `coil` and `discrete` registers the field-value is output as zero or
|
|
|
|
|
one in `UINT16` format.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
#### per-field measurement setting
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
The `measurement` setting can be used to override the measurement name on a
|
|
|
|
|
per-field basis. This might be useful if you want to split the fields in one
|
|
|
|
|
request to multiple measurements. If not specified, the value specified in the
|
|
|
|
|
[`request` section](#per-request-measurement-setting) or, if also omitted,
|
|
|
|
|
`modbus` is used.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
This setting is ignored if the field's `omit` is set to `true` and can be
|
|
|
|
|
omitted in this case.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
|
|
|
|
#### omitting a field
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
When specifying `omit=true`, the corresponding field will be ignored when
|
|
|
|
|
collecting the metric but is taken into account when constructing the modbus
|
|
|
|
|
requests. This way, you can fill "holes" in the addresses to construct
|
|
|
|
|
consecutive address ranges resulting in a single request. Using a single modbus
|
|
|
|
|
request can be beneficial as the values are all collected at the same point in
|
|
|
|
|
time.
|
2021-12-03 06:06:06 +08:00
|
|
|
|
2021-12-09 03:19:13 +08:00
|
|
|
#### Tags definitions
|
|
|
|
|
|
|
|
|
|
Each `request` can be accompanied by tags valid for this request.
|
2022-06-09 05:22:56 +08:00
|
|
|
|
|
|
|
|
__Please note:__ These tags take precedence over predefined tags such as `name`,
|
|
|
|
|
`type` or `slave_id`.
|
2021-12-09 03:19:13 +08:00
|
|
|
|
2021-12-03 06:06:06 +08:00
|
|
|
---
|
|
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
## Metrics
|
|
|
|
|
|
|
|
|
|
Metrics are custom and configured using the `discrete_inputs`, `coils`,
|
|
|
|
|
`holding_register` and `input_registers` options.
|
|
|
|
|
|
2022-01-25 02:22:07 +08:00
|
|
|
## Troubleshooting
|
2021-11-25 03:18:53 +08:00
|
|
|
|
|
|
|
|
### Strange data
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
Modbus documentation is often a mess. People confuse memory-address (starts at
|
|
|
|
|
one) and register address (starts at zero) or are unsure about the word-order
|
|
|
|
|
used. Furthermore, there are some non-standard implementations that also swap
|
|
|
|
|
the bytes within the register word (16-bit).
|
2021-05-28 04:58:46 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
If you get an error or don't get the expected values from your device, you can
|
|
|
|
|
try the following steps (assuming a 32-bit value).
|
2021-05-28 04:58:46 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
If you are using a serial device and get a `permission denied` error, check the
|
|
|
|
|
permissions of your serial device and change them accordingly.
|
2021-05-28 04:58:46 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
In case you get an `exception '2' (illegal data address)` error you might try to
|
|
|
|
|
offset your `address` entries by minus one as it is very likely that there is
|
|
|
|
|
confusion between memory and register addresses.
|
2021-05-28 04:58:46 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
If you see strange values, the `byte_order` might be wrong. You can either probe
|
|
|
|
|
all combinations (`ABCD`, `CDBA`, `BADC` or `DCBA`) or set `byte_order="ABCD"
|
|
|
|
|
data_type="UINT32"` and use the resulting value(s) in an online converter like
|
|
|
|
|
[this][online-converter]. This especially makes sense if you don't want to mess
|
|
|
|
|
with the device, deal with 64-bit values and/or don't know the `data_type` of
|
|
|
|
|
your register (e.g. fix-point floating values vs. IEEE floating point).
|
2021-05-28 04:58:46 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
If your data still looks corrupted, please post your configuration, error
|
|
|
|
|
message and/or the output of `byte_order="ABCD" data_type="UINT32"` to one of
|
|
|
|
|
the telegraf support channels (forum, slack or as an issue). If nothing helps,
|
|
|
|
|
please post your configuration, error message and/or the output of
|
|
|
|
|
`byte_order="ABCD" data_type="UINT32"` to one of the telegraf support channels
|
|
|
|
|
(forum, slack or as an issue).
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
[online-converter]: https://www.scadacore.com/tools/programming-calculators/online-hex-converter/
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
### Workarounds
|
2021-10-20 05:12:13 +08:00
|
|
|
|
2022-06-09 05:22:56 +08:00
|
|
|
Some Modbus devices need special read characteristics when reading data and will
|
|
|
|
|
fail otherwise. For example, some serial devices need a pause between register
|
|
|
|
|
read requests. Others might only support a limited number of simultaneously
|
|
|
|
|
connected devices, like serial devices or some ModbusTCP devices. In case you
|
|
|
|
|
need to access those devices in parallel you might want to disconnect
|
|
|
|
|
immediately after the plugin finishes reading.
|
|
|
|
|
|
|
|
|
|
To enable this plugin to also handle those "special" devices, there is the
|
|
|
|
|
`workarounds` configuration option. In case your documentation states certain
|
|
|
|
|
read requirements or you get read timeouts or other read errors, you might want
|
|
|
|
|
to try one or more workaround options. If you find that other/more workarounds
|
|
|
|
|
are required for your device, please let us know.
|
|
|
|
|
|
|
|
|
|
In case your device needs a workaround that is not yet implemented, please open
|
|
|
|
|
an issue or submit a pull-request.
|
2021-05-28 04:58:46 +08:00
|
|
|
|
2021-11-25 03:18:53 +08:00
|
|
|
## Example Output
|
2020-01-29 18:18:58 +08:00
|
|
|
|
2020-08-11 03:50:48 +08:00
|
|
|
```sh
|
2020-01-29 18:18:58 +08:00
|
|
|
$ ./telegraf -config telegraf.conf -input-filter modbus -test
|
|
|
|
|
modbus.InputRegisters,host=orangepizero Current=0,Energy=0,Frecuency=60,Power=0,PowerFactor=0,Voltage=123.9000015258789 1554079521000000000
|
|
|
|
|
```
|