telegraf/plugins/inputs/modbus/sample_general_begin.conf

47 lines
1.5 KiB
Plaintext
Raw Normal View History

# Retrieve data from MODBUS slave devices
[[inputs.modbus]]
## Connection Configuration
##
## The plugin supports connections to PLCs via MODBUS/TCP, RTU over TCP, ASCII over TCP or
## via serial line communication in binary (RTU) or readable (ASCII) encoding
##
## Device name
name = "Device"
## Slave ID - addresses a MODBUS device on the bus
## Range: 0 - 255 [0 = broadcast; 248 - 255 = reserved]
slave_id = 1
## Timeout for each request
timeout = "1s"
## Maximum number of retries and the time to wait between retries
## when a slave-device is busy.
# busy_retries = 0
# busy_retries_wait = "100ms"
# TCP - connect via Modbus/TCP
controller = "tcp://localhost:502"
## Serial (RS485; RS232)
# controller = "file:///dev/ttyUSB0"
# baud_rate = 9600
# data_bits = 8
# parity = "N"
# stop_bits = 1
## For Modbus over TCP you can choose between "TCP", "RTUoverTCP" and "ASCIIoverTCP"
## default behaviour is "TCP" if the controller is TCP
## For Serial you can choose between "RTU" and "ASCII"
# transmission_mode = "RTU"
## Trace the connection to the modbus device as debug messages
## Note: You have to enable telegraf's debug mode to see those messages!
# debug_connection = false
## Define the configuration schema
## |---register -- define fields per register type in the original style (only supports one slave ID)
## |---request -- define fields on a requests base
configuration_type = "register"