You can debug Modbus connection issues by enabling `debug_connection`. To see those debug messages, Telegraf has to be started with debugging enabled (i.e. with the `--debug` option). Please be aware that connection tracing will produce a lot of messages and should **NOT** be used in production environments.
Please use `pause_between_requests` with care. Ensure the total gather time, including the pause(s), does not exceed the configured collection interval. Note that pauses add up if multiple requests are sent!
The modbus plugin supports multiple configuration styles that can be set using the `configuration_type` setting. The different styles are described below. Please note that styles cannot be mixed, i.e. only the settings belonging to the configured `configuration_type` are used for constructing _modbus_ requests and creation of metrics.
This sytle can be used to specify the modbus requests directly. It enables specifying multiple `[[inputs.modbus.request]]` sections including multiple slave-devices. This way, _modbus_ gateway devices can be queried. Please note that _requests_ might be split for non-consecutive addresses. If you want to avoid this behavior please add _fields_ with the `omit` flag set filling the gaps between addresses.
You can use the `slave_id` setting to specify the ID of the slave device to query. It should be specified for each request, otherwise it defaults to zero. Please note, only one `slave_id` can be specified per request.
The `byte_order` setting specifies the byte and word-order of the registers. It can be set to `ABCD` for _big endian (Motorola)_ or `DCBA` for _little endian (Intel)_ format as well as `BADC` and `CDAB` for _big endian_ or _little endian_ with _byte swap_.
The `register` setting specifies the modbus register-set to query and can be set to `coil`, `discrete`, `holding` or `input`.
#### Per-request measurement setting
You can specify the name of the measurement for the following field definitions using the `measurement` setting. If the setting is omitted `modbus` is used. Furthermore, the measurement value can be overridden by each field individually.
#### Field definitions
Each `request` can contain a list of fields to collect from the modbus device.
##### address
A field is identified by an `address` that reflects the modbus register address. You can usually find the address values for the different datapoints in the datasheet of your modbus device. This is a mandatory setting.
For _coil_ and _discrete input_ registers this setting specifies the __bit__ containing the value of the field.
##### name
Using the `name` setting you can specify the field-name in the metric as output by the plugin. This setting is ignored if the field's `omit` is set to `true` and can be omitted in this case.
__Please note:__ There cannot be multiple fields with the same `name` in one metric identified by `measurement`, `slave_id` and `register`.
##### register datatype
The `register` setting specifies the datatype of the modbus register and can be set to `INT16`, `UINT16`, `INT32`, `UINT32`, `INT64` or `UINT64` for integer types or `FLOAT32` and `FLOAT64` for IEEE 754 binary representations of floating point values. Usually the datatype of the register is listed in the datasheet of your modbus device in relation to the `address` described above.
This setting is ignored if the field's `omit` is set to `true` or if the `register` type is a bit-type (`coil` or `discrete`) and can be omitted in these cases.
You can use the `scale` setting to scale the register values, e.g. if the register contains a fix-point values in `UINT32` format with two decimal places for example. To convert the read register value to the actual value you can set the `scale=0.01`. The scale is used as a factor e.g. `field_value * scale`.
This setting is ignored if the field's `omit` is set to `true` or if the `register` type is a bit-type (`coil` or `discrete`) and can be omitted in these cases.
__Please note:__ The resulting field-type will be set to `FLOAT64` if no output format is specified.
Using the `output` setting you can explicitly specify the output field-datatype. The `output` type can be `INT64`, `UINT64` or `FLOAT64`. If not set explicitly, the output type is guessed as follows: If `scale` is set to a non-zero value, the output type is `FLOAT64`. Otherwise, the output type corresponds to the register datatype _class_, i.e. `INT*` will result in `INT64`, `UINT*` in `UINT64` and `FLOAT*` in `FLOAT64`.
This setting is ignored if the field's `omit` is set to `true` or if the `register` type is a bit-type (`coil` or `discrete`) and can be omitted in these cases. For `coil` and `discrete` registers the field-value is output as zero or one in `UINT16` format.
The `measurement` setting can be used to override the measurement name on a per-field basis. This might be useful if you want to split the fields in one request to multiple measurements. If not specified, the value specified in the [`request` section](#per-request-measurement-setting) or, if also omitted, `modbus` is used.
This setting is ignored if the field's `omit` is set to `true` and can be omitted in this case.
#### omitting a field
When specifying `omit=true`, the corresponding field will be ignored when collecting the metric but is taken into account when constructing the modbus requests. This way, you can fill "holes" in the addresses to construct consecutive address ranges resulting in a single request. Using a single modbus request can be beneficial as the values are all collected at the same point in time.
Modbus documentation is often a mess. People confuse memory-address (starts at one) and register address (starts at zero) or are unsure about the word-order used. Furthermore, there are some non-standard implementations that also swap the bytes within the register word (16-bit).
In case you get an `exception '2' (illegal data address)` error you might try to offset your `address` entries by minus one as it is very likely that there is confusion between memory and register addresses.
If you see strange values, the `byte_order` might be wrong. You can either probe all combinations (`ABCD`, `CDBA`, `BADC` or `DCBA`) or set `byte_order="ABCD" data_type="UINT32"` and use the resulting value(s) in an online converter like [this](https://www.scadacore.com/tools/programming-calculators/online-hex-converter/). This especially makes sense if you don't want to mess with the device, deal with 64-bit values and/or don't know the `data_type` of your register (e.g. fix-point floating values vs. IEEE floating point).
If your data still looks corrupted, please post your configuration, error message and/or the output of `byte_order="ABCD" data_type="UINT32"` to one of the telegraf support channels (forum, slack or as an issue).
If nothing helps, please post your configuration, error message and/or the output of `byte_order="ABCD" data_type="UINT32"` to one of the telegraf support channels (forum, slack or as an issue).
Some Modbus devices need special read characteristics when reading data and will fail otherwise. For example, some serial devices need a pause between register read requests. Others might only support a limited number of simultaneously connected devices, like serial devices or some ModbusTCP devices. In case you need to access those devices in parallel you might want to disconnect immediately after the plugin finishes reading.
To enable this plugin to also handle those "special" devices, there is the `workarounds` configuration option. In case your documentation states certain read requirements or you get read timeouts or other read errors, you might want to try one or more workaround options.