# Retrieve data from OPCUA devices [[inputs.opcua]] ## Metric name # name = "opcua" # ## OPC UA Endpoint URL # endpoint = "opc.tcp://localhost:4840" # ## Maximum time allowed to establish a connect to the endpoint. # connect_timeout = "10s" # ## Maximum time allowed for a request over the estabilished connection. # request_timeout = "5s" # ## Security policy, one of "None", "Basic128Rsa15", "Basic256", ## "Basic256Sha256", or "auto" # security_policy = "auto" # ## Security mode, one of "None", "Sign", "SignAndEncrypt", or "auto" # security_mode = "auto" # ## Path to cert.pem. Required when security mode or policy isn't "None". ## If cert path is not supplied, self-signed cert and key will be generated. # certificate = "/etc/telegraf/cert.pem" # ## Path to private key.pem. Required when security mode or policy isn't "None". ## If key path is not supplied, self-signed cert and key will be generated. # private_key = "/etc/telegraf/key.pem" # ## Authentication Method, one of "Certificate", "UserName", or "Anonymous". To ## authenticate using a specific ID, select 'Certificate' or 'UserName' # auth_method = "Anonymous" # ## Username. Required for auth_method = "UserName" # username = "" # ## Password. Required for auth_method = "UserName" # password = "" # ## Option to select the metric timestamp to use. Valid options are: ## "gather" -- uses the time of receiving the data in telegraf ## "server" -- uses the timestamp provided by the server ## "source" -- uses the timestamp provided by the source # timestamp = "gather" # ## Node ID configuration ## name - field name to use in the output ## namespace - OPC UA namespace of the node (integer value 0 thru 3) ## identifier_type - OPC UA ID type (s=string, i=numeric, g=guid, b=opaque) ## identifier - OPC UA ID (tag as shown in opcua browser) ## tags - extra tags to be added to the output metric (optional) ## Example: ## {name="ProductUri", namespace="0", identifier_type="i", identifier="2262", tags=[["tag1","value1"],["tag2","value2]]} # nodes = [ # {name="", namespace="", identifier_type="", identifier=""}, # {name="", namespace="", identifier_type="", identifier=""}, #] # ## Node Group ## Sets defaults for OPC UA namespace and ID type so they aren't required in ## every node. A group can also have a metric name that overrides the main ## plugin metric name. ## ## Multiple node groups are allowed #[[inputs.opcua.group]] ## Group Metric name. Overrides the top level name. If unset, the ## top level name is used. # name = # ## Group default namespace. If a node in the group doesn't set its ## namespace, this is used. # namespace = # ## Group default identifier type. If a node in the group doesn't set its ## namespace, this is used. # identifier_type = # ## Node ID Configuration. Array of nodes with the same settings as above. # nodes = [ # {name="", namespace="", identifier_type="", identifier=""}, # {name="", namespace="", identifier_type="", identifier=""}, #] ## Enable workarounds required by some devices to work correctly # [inputs.opcua.workarounds] ## Set additional valid status codes, StatusOK (0x0) is always considered valid # additional_valid_status_codes = ["0xC0"]