UPSD Input Plugin

This plugin reads data of one or more Uninterruptible Power Supplies from an upsd daemon using its NUT network protocol.

Requirements

upsd should be installed and it's daemon should be running.

Global configuration options

In addition to the plugin-specific configuration settings, plugins support additional global and plugin configuration settings. These settings are used to modify metrics, tags, and field or create aliases and configure ordering, etc. See the CONFIGURATION.md for more details.

Configuration

# Monitor UPSes connected via Network UPS Tools
[[inputs.upsd]]
  ## A running NUT server to connect to.
  ## IPv6 addresses must be enclosed in brackets (e.g. "[::1]")
  # server = "127.0.0.1"
  # port = 3493
  # username = "user"
  # password = "password"

  ## Force parsing numbers as floats
  ## It is highly recommended to enable this setting to parse numbers
  ## consistently as floats to avoid database conflicts where some numbers are
  ## parsed as integers and others as floats.
  # force_float = false

  ## Collect additional fields if they are available for the UPS
  ## The fields need to be specified as NUT variable names, see
  ## https://networkupstools.org/docs/developer-guide.chunked/apas02.html
  ## Wildcards are accepted.
  # additional_fields = []

  ## Dump information for debugging
  ## Allows to print the raw variables (and corresponding types) as received
  ## from the NUT server ONCE for each UPS. The output is only available when
  ## running Telegraf in debug-mode.
  ## Please attach this information when reporting issues!
  # dump_raw_variables = false

Metrics

This implementation tries to maintain compatibility with the apcupsd metrics:

  • upsd
    • tags:
      • serial
      • ups_name
      • model
    • fields:
      • status_flags (status-bits)
      • input_voltage
      • load_percent
      • battery_charge_percent
      • time_left_ns
      • output_voltage
      • internal_temp
      • battery_voltage
      • input_frequency
      • battery_date
      • nominal_input_voltage
      • nominal_battery_voltage
      • nominal_power
      • firmware

With the exception of:

  • tags:
    • status (string representing the set status_flags)
  • fields:
    • time_on_battery_ns

Example Output

upsd,serial=AS1231515,ups_name=name1 load_percent=9.7,time_left_ns=9800000,output_voltage=230.4,internal_temp=32.4,battery_voltage=27.4,input_frequency=50.2,input_voltage=230.4,battery_charge_percent=100,status_flags=8i 1490035922000000000